 KYN28A-12 Gas Insulated Middle-Mounted Metal Clad &Enclosed HV Electrical Switchgear

1.General 

KYN28A-12(GZs1-12Z) Gas Insulated Metal Armoured/ clad Middle-Mounted Enclosed High voltage switchgear (hereinafter referred to as switchgear) is a new product with own design and development on the basis of absorbing advanced technology abroad, it can replace the old metal enclosed switchgears, such as KYN1-10, JYN2-10, GBC-10 series, etc.
The shell is bolted by Al-Zn alloy coated steel plates which are formed after multiple bending by CNC machine tool to ensure not only the high mechanical strength, but also the tidy and beautiful product. The door is plastic sprayed to ensure the high impact resistance and corrosion resistance ability. The protection level of is IP4X.  
The main switch can be configured VD4-type vacuum circuit breaker, C3 series fixed load switch, meanwhile, it also can be assembled several domestic vacuum circuit breakers (such as VS1, VH1, VK, ZN28) to replace the similar products.
No matter which kind of circuit breaker is chosen, the air insulation distance should be more than 125mm, the composite insulation distance should be greater than 60mm.

There are interlock protection functions to prevent operating CB trolley with load, prevent misoperation of CB, prevent closing CB with earthing switch closed, prevent entering electrified chamber and prevent closing earthing switch with power.

2.Model Definition 

 

3.Operational Environment 

a. Ambient Temperature: -10℃~+45℃
b. Relative Humidity: Daily average should be less than 95%, monthly average is not more than 90%
c. Altitude: Not higher than 1000m, if more than 1000, decrease capacity according to the altitude.

d. The seismic intensity should be less than 8-magnitude.
e. It should be operated in the place without danger of fire, explosion, serious dirtiness, chemical corrosion and acute shaking.
If it is planed to operate in the condition out of the above limits, the customers should negotiate with us to decide the allowable operational conditions and technical measures.

4. Technical Parameters 

Item

Unit

Parameters

Rated voltage

kV

3, 6, 7.2,12

Rated frequency 

Hz

50

CB rated current

A

630,  1250, 1600, 2000, 2500, 3150, 4000

Switchgear rated current

A

630,  1250, 1600, 2000, 2500, 3150, 4000

Short-time withstand current

kA

20, 25, 31.5, 40, 50

Rated dynamic stability current(peak)

kA

50, 63, 80, 100, 125

Rated short circuit breaking current

kA

20, 25, 31.5, 40, 50

Rated short circuit closed current

kA

50, 63, 80, 100, 125

 

Rated insulation grade

1min power frequency withstand voltage

kV

42

Lightning impulse withstand voltage

kV

75

Protection level

Shell: IP4X, isolation chamber and CB chamber door opened: IP2X.

 

 

5. Metal Enclosed Switchgear Schematic Diagram 


1  -Shell  

2  -Branch bar 

3  -Busbar 

4  -Isolated contacts

5  -Contact box 

6  -Earthing switch

7  -Current transformer

8  -Zinc oxide arrester

9  -Base plate

10-main grounding busbar

11-The control line slot


A Busbar chamber   

B CB Chamber


12-Cable seal terminal

13-Earthing switch operating mechanism

14-Detachable horizontal clapboard

15-Wire rod mechanism 

16-VCB

17- Secondary plug

18-Terminal board

19-Shutter

20-detachable clapboard

21-Pressure release 

C Cable Chamber       

D Relay instrument chamber



6. Overview of switchgear structure

CB chamber

Railways have been installed on both sides of chamber, the trolley slides on it from disconnecting/testing position to working position in electrical cabinet. The shutter of fixed contact box has been installed behind the trolley chamber. when moving trolley from disconnecting/testing position to working position, the shutters of upper and lower fixed contact box opened together automatically and closed automatically. If move trolley from working position to disconnecting/testing position, they will cover fixed contact box completely until the trolley has been moved back to specified position and ensure effective isolation. At the same time, because the upper and lower shutters can not be moved together, so the maintenance people may lock the shutter of electrified side to keep them away from electrified part. The trolley may be operated when the door of circuit breaker chamber closed. The maintenance people may observe the trolley’s location, closing and opening indication and charging condition through window on door.

Busbar chamber

Main busbars are connected together and run through Metal Enclosed switchgear, which fixed by branch busbar and fixed contactor box. The main and inter busbar are copper material with rectangle section, and adopted double busbars due to high current load. The branch busbar is connected to fixed contactor box and main busbar by bolts, it does not other support. For special requirement, the busbar can be covered by heat-shrinkable bush, insulating bushing and side-cap. The busbar of neighboring cabinets are fixed by bushing. The air-cushion kept between inter busbars will prevent busbars from melting if internal fault arc appears. The bushing will limit failure effectively not expanding to other switchgear.

Cable chamber

The gas insulated switchgear is adopted central-mounted type, so the cable chamber has enough space. The current transformer and earthing switch have been mounted behind chamber. Lightning arrestor has been mounted on back and lower part of chamber. People will enter cabinet from front to install and maintain after moved trolley and withdrawable clapboard away. The switchgear connected with cables is equipped with movable non-metal or non-magnetic metal seal plates with crack at the bottom to ensure the convenience to construction. 

Relay and instrument chamber

The relay and instrument chamber can be installed with protective elements, meter supervision indicator and secondary equipment with special requirement. The control wires were laid in wire slot with enough space, and covered with the metal plate to separate secondary wire and HV chamber. The holes have been reserved at the roof of relay and instrument chamber for construction of small busbar. When wiring, the roof plate of meter chamber can be rotated, that is convenient to install small busbar. 

7. Interlock protection

1. The circuit breaker only can be closed and opened when the circuit breaker trolley is at testing or working position and the trolley can not be moved after closed circuit breaker, this function prevents pulling and pushing circuit breaker with load.

2. The circuit breaker trolley only can be moved from testing/opening position to working position when the earthing switch is at opening position. The earthing switch only can be closed (may be fitted with charged display device) when circuit breaker trolley is rotated to testing/opening position. This function prevents earthing switch from mistake-closing with load, and prevents maintainer from closing circuit breaker while the earthing switch was on closing position.

3. The back door and lower door can not be opened when the earthing switch is at opening position, and this function prevents maintenance people from entering working compartment (electrified) in error.

4. When the circuit breaker trolley is rotated to testing or working position without control voltage, and it can only be opened manually, but not closed.

5. When the circuit breaker trolley is at working position, the secondary plugs has been locked and can not be moved.

8. Installation Dimensions 

Switchgear usage

Width

Wire in and out at bottom depth

Wire in and out on top depth

CB cabinet

650

1500(1550)

1660

800

1000

PT cabinet

800

1500(1550)

1660

Meter cabinet

800

1500(1550)

1660

*If the users has requirements on dimensions, please note when order.

 

 9. Ordering Instructions 

 Orderers should offer the following technical information: 

a. Main wiring diagram plan No., use and single line diagram, rated voltage, rated current, rated short-circuit breaking current, distribution room layout and switchgears arrangement diagrams, etc.
b. The switchgear control, measurement and protection functional requirements; other blocking and automatic device requirements and schematic diagrams

c. The type, specification and quantity of main electrical elements installed in the switchgear.
d. Other special requirements. 

10. Certificate

 

XD HI-TECH, established 2007, is one of the excellent manufacturers in China. Come and find china kyn28a-12 gas insulated middle-mounted metal clad & enclosed hv electrical cabinet/switchgear manufacturer from our factory. Coming in high precision, and good performance, our custom products have a wide application field. Welcome to wholesale our quality products and the PDF display is also offered.